%PDF-1.5 % 1 0 obj<>/PageLabels 5486 0 R/AcroForm 8035 0 R>> endobj 2 0 obj<> endobj 161 0 obj<> endobj 5486 0 obj<> 1<
> 2<>]>> endobj 5489 0 obj<>/ExtGState<>/ProcSet[/PDF/Text/ImageB/ImageC/ImageI]/XObject<>>>/MediaBox[0 0 612 792]/Contents[6981 0 R 6980 0 R 6979 0 R 6978 0 R 6977 0 R 6976 0 R 9732 0 R]/Group<>/Tabs/S/StructParents 25/Annots 5490 0 R>> endobj 5490 0 obj[6972 0 R 6967 0 R 6962 0 R 6957 0 R 6952 0 R 6947 0 R 6942 0 R 6937 0 R 6932 0 R 6927 0 R 6922 0 R 6917 0 R 6912 0 R 6907 0 R 6902 0 R 6897 0 R 6892 0 R 6887 0 R 6882 0 R 6877 0 R 6872 0 R 6867 0 R 6862 0 R 6857 0 R 6852 0 R 6847 0 R 6842 0 R 6837 0 R 6830 0 R 6824 0 R 6818 0 R 6812 0 R 6806 0 R 6800 0 R 6793 0 R 6787 0 R 6781 0 R 6775 0 R 6769 0 R 6763 0 R 6757 0 R 6751 0 R 6745 0 R 6739 0 R 6733 0 R 6727 0 R 6721 0 R 6715 0 R 6709 0 R 6703 0 R 6697 0 R 6691 0 R 6685 0 R 6679 0 R 6673 0 R 6667 0 R 6661 0 R 6655 0 R 6649 0 R 6643 0 R 6637 0 R 6631 0 R 6625 0 R 6619 0 R 6613 0 R 6607 0 R 6601 0 R 6595 0 R 6589 0 R 6583 0 R 6577 0 R 6571 0 R 6565 0 R 6559 0 R 6553 0 R 6547 0 R 6541 0 R 6535 0 R 6529 0 R 6523 0 R 6517 0 R 6511 0 R 6505 0 R 6499 0 R 6493 0 R 6487 0 R 6481 0 R 6475 0 R 6469 0 R 6463 0 R 6457 0 R 6451 0 R 6445 0 R 6439 0 R 6433 0 R 6427 0 R 6421 0 R 6415 0 R 6409 0 R 6403 0 R 6397 0 R 6391 0 R 6385 0 R 6379 0 R 6373 0 R 6367 0 R 6361 0 R 6355 0 R 6349 0 R 6343 0 R 6337 0 R 6331 0 R 6325 0 R 6319 0 R 6313 0 R 6307 0 R 6301 0 R 6295 0 R 6289 0 R 6283 0 R 6277 0 R 6271 0 R 6265 0 R 6259 0 R 6253 0 R 6247 0 R 6241 0 R 6235 0 R 6229 0 R 6223 0 R 6217 0 R 6211 0 R 6205 0 R 6200 0 R 6195 0 R 6190 0 R 6185 0 R 6180 0 R 6175 0 R 6170 0 R 6165 0 R 6160 0 R 6155 0 R 6150 0 R 6145 0 R 6140 0 R 6135 0 R 6130 0 R 6125 0 R 6120 0 R 6115 0 R 6110 0 R 6105 0 R 6100 0 R 6095 0 R 6090 0 R 6085 0 R 6080 0 R 6075 0 R 6070 0 R 6065 0 R 6060 0 R 5545 0 R 6055 0 R 6050 0 R 6045 0 R 6040 0 R 6035 0 R 6030 0 R 6025 0 R 6020 0 R 6015 0 R 6010 0 R 6005 0 R 6000 0 R 5995 0 R 5990 0 R 5985 0 R 5980 0 R 5975 0 R 5970 0 R 5965 0 R 5960 0 R 5955 0 R 5950 0 R 5945 0 R 5940 0 R 5935 0 R 5930 0 R 5925 0 R 5920 0 R 5915 0 R 5910 0 R 5905 0 R 5900 0 R 5895 0 R 5890 0 R 5885 0 R 5880 0 R 5875 0 R 5870 0 R 5865 0 R 5860 0 R 5855 0 R 5850 0 R 5845 0 R 5840 0 R 5835 0 R 5830 0 R 5825 0 R 5820 0 R 5815 0 R 5810 0 R 5805 0 R 5800 0 R 5795 0 R 5790 0 R 5785 0 R 5780 0 R 5775 0 R 5770 0 R 5765 0 R 5760 0 R 5755 0 R 5750 0 R 5745 0 R 5740 0 R 5735 0 R 5730 0 R 5725 0 R 5720 0 R 5715 0 R 5710 0 R 5705 0 R 5700 0 R 5695 0 R 5690 0 R 5685 0 R 5680 0 R 5675 0 R 5670 0 R 5665 0 R 5660 0 R 5655 0 R 5650 0 R 5645 0 R 5640 0 R 5635 0 R 5630 0 R 5625 0 R 5620 0 R 5615 0 R 5610 0 R 5605 0 R 5600 0 R 5595 0 R 5590 0 R 5585 0 R 5580 0 R 5575 0 R 5570 0 R 5565 0 R 5560 0 R 5555 0 R 5550 0 R 5544 0 R 5539 0 R 5533 0 R 5527 0 R 5522 0 R 5506 0 R 5501 0 R 5496 0 R 5491 0 R] endobj 5491 0 obj<The plans shall contain only information required for this permit. Information that relates to other permits shall not be on this set of plans.
)/Contents(The plans shall contain only information required for this permit. Information that relates to other permits shall not be on this set of plans.)/M(D:20190814130816-04'00')/AP<>/NM(WABDPDKRTQRXIBFO)>> endobj 5492 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4In type \215B\216 dwelling units: All lighting controls, electrical switches and receptacle outlets, electrical panelboards, environmental controls and user controls for security or intercom systems shall comply with Section 309. Show clear space and mounting heights on the plans. [ICC A117.1-2009]
)/Contents(In type \215B\216 dwelling units: All lighting controls, electrical switches and receptacle outlets, electrical panelboards, environmental controls and user controls for security or intercom systems shall comply with Section 309. Show clear space and mounting heights on the plans. [ICC A117.1-2009])/M(D:20190814130816-04'00')/AP<>/NM(WJVVAUIRZVETJIUK)>> endobj 5497 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4In type \215A\216 dwelling units: All lighting controls, electrical switches and receptacle outlets, electrical panelboards, environmental controls, appliance controls and user controls for security or intercom systems shall comply with Section 309. Show clear space and mounting heights on the plans. [ICC A117.1-2009]
)/Contents(In type \215A\216 dwelling units: All lighting controls, electrical switches and receptacle outlets, electrical panelboards, environmental controls, appliance controls and user controls for security or intercom systems shall comply with Section 309. Show clear space and mounting heights on the plans. [ICC A117.1-2009])/M(D:20190814130816-04'00')/AP<>/NM(SNHAMXILQVYMIXDB)>> endobj 5502 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Label all type \215A\216 and \215B\216 accessible dwelling units on the plans. [VCC Section 1107]
)/Contents(Label all type \215A\216 and \215B\216 accessible dwelling units on the plans. [VCC Section 1107])/M(D:20190814130816-04'00')/AP<>/NM(QMGUJBKGSKJDRYKB)>> endobj 5507 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4In buildings where a required accessible floor is four or more stories above or below a level of exit discharge, at least one required accessible means of egress shall be an elevator complying with IBC Section 1007.4. [VCC 1007.2.1]
)/Contents(In buildings where a required accessible floor is four or more stories above or below a level of exit discharge, at least one required accessible means of egress shall be an elevator complying with IBC Section 1007.4. [VCC 1007.2.1])/M(D:20190814130816-04'00')/AP<>/NM(KBSCEQTNYIFZTNUE)>> endobj 5540 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide revision triangles with number, description and date. See Annex B-E1 for an example \(For space reason, the date and description is not shown on the example, just the revision triangle\).
)/Contents(Provide revision triangles with number, description and date. See Annex B-E1 for an example \(For space reason, the date and description is not shown on the example, just the revision triangle\). )/M(D:20190814130816-04'00')/AP<>/NM(YWQISOHEWZXDYHFV)/Popup 5544 0 R>> endobj 5546 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4All plans shall have a 3.5\216 x 2\216 clear area for City of Richmond approval stamp. Do not add a box for this area, just make sure you have at least the required 3.5\216 x 2\216 area.
)/ContentsProvide a completed checklist \(Pages 25 through 26\) with all applicable items checked. The Checklist shall be signed by either the Contractor/Master Electrician OR signed/sealed by the Engineer or record.
)/Contents(Provide a completed checklist \(Pages 25 through 26\) with all applicable items checked. The Checklist shall be signed by either the Contractor/Master Electrician OR signed/sealed by the Engineer or record.)/M(D:20190814130816-04'00')/AP<>/NM(ZSRGBKJEFYIGXOTL)>> endobj 5556 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Show, label and provide description for all new and revised equipment/appliance/device/lighting on the
plan\(s\). For buildings with multiple tenants/dwelling units, label the tenant/dwelling unit next to equipment that is not specifically located in each tenant/dwelling unit. [NEC 110.26, VCC 109.3]
)/ContentsProvide coordination study for all legally required standby loads. See Section D-1 for the City\220s requirements. [NEC 701.27]
)/Contents(Provide coordination study for all legally required standby loads. See Section D-1 for the City\220s requirements. [NEC 701.27])/M(D:20190814130816-04'00')/AP<>/NM(NCJFRFVOPAEMPGKV)>> endobj 5566 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4In buildings where a required accessible floor is four or more stories above or below a level of exit discharge, at least one required accessible means of egress shall be an elevator complying with IBC Section 1007.4. [VCC 1009.2.1]
)/Contents(In buildings where a required accessible floor is four or more stories above or below a level of exit discharge, at least one required accessible means of egress shall be an elevator complying with IBC Section 1007.4. [VCC 1009.2.1])/M(D:20190814130816-04'00')/AP<>/NM(CXYYCEZDOIZJEIYW)>> endobj 5571 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide coordination study for all legally required standby loads. See Section D-1 for the City\220s requirements. [NEC 701.27]
)/Contents(Provide coordination study for all legally required standby loads. See Section D-1 for the City\220s requirements. [NEC 701.27])/M(D:20190814130816-04'00')/AP<>/NM(KFLTLKBCZNGAAIKR)>> endobj 5576 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide proper disconnecting means for outside generator on the plans. [NEC 701.12\(B\)\(5\)]
)/Contents(Provide proper disconnecting means for outside generator on the plans. [NEC 701.12\(B\)\(5\)])/M(D:20190814130816-04'00')/AP<>/NM(WIVPQSHMNOSNSVOS)>> endobj 5581 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide sufficient details on the plans to show how the emergency systems will be protected from complete failure due to fire, flood, icing, and vandalism. [NEC 701.12]
)/Contents(Provide sufficient details on the plans to show how the emergency systems will be protected from complete failure due to fire, flood, icing, and vandalism. [NEC 701.12])/M(D:20190814130816-04'00')/AP<>/NM(JNFNSBXHCUUJIPRW)>> endobj 5586 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide coordination study for all emergency loads. Coordination shall be for the emergency overcurrent protection device\(s\) and all supply side overcurrent protection devices. See Section D-1 for the City\220s requirements. [NEC 700.28]
)/Contents(Provide coordination study for all emergency loads. Coordination shall be for the emergency overcurrent protection device\(s\) and all supply side overcurrent protection devices. See Section D-1 for the City\220s requirements. [NEC 700.28])/M(D:20190814130816-04'00')/AP<>/NM(OOPGZLHUUEHNQZTB)>> endobj 5591 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Plans shall show all specific requirements for unit equipment. See exception in Article 700.12\(F\). [NEC 700.12\(F\)]
)/Contents(Plans shall show all specific requirements for unit equipment. See exception in Article 700.12\(F\). [NEC 700.12\(F\)])/M(D:20190814130816-04'00')/AP<>/NM(IBPPZWKURBNBEGXY)>> endobj 5596 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide sufficient details on the plans to show how the emergency systems will be protected from complete failure due to fire, flood, icing, and vandalism. [NEC 700.12]
)/ContentsProvide means on the plans to show separation of emergency wiring and equipment from all other wiring. [NEC 700.10\(B\)]
)/Contents(Provide means on the plans to show separation of emergency wiring and equipment from all other wiring. [NEC 700.10\(B\)])/M(D:20190814130816-04'00')/AP<>/NM(UMDXDSSYEWWPXWWL)>> endobj 5606 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Prior to final inspection, all projects that require emergency lighting shall have either \(i\) or \(ii\) below:
\(i\) A master electrician, or a professional engineer shall provide the City with a signed copy of the Emergency Lighting Test Checklist located in ANNEX E stating that all emergency lighting test meets or exceeds IBC for normal and emergency power based on Sections 1006.2 and 1006.3.1 of the IBC.
OR
\(ii\) Provide normal and emergency lighting photometrics on the electrical plan\(s\). Show photometrics for areas that are part of the path of egress only. Provide, on the electrical plan\(s\), the method of determining the photometrics and all total light loss factors, lamp lumen depreciation, luminaire dirt depreciation, and ballast factor utilized in the calculations. For both normal and emergency photometrics, provide maximum and minimum illumination levels, as well as the maximum to minimum ratio. For battery operated emergency lighting, specify on the plan\(s\) that the lighting will not have lower than an average of 0.6 footcandles after 90 minutes of operation. [VCC 1008.2, 1008.3.5, 1007]
)/ContentsProvide exterior egress lighting at all egress exits. Exterior egress fixtures shall be connected to life safety and/or battery-back up. If existing, provide this information on the plans. [VCC 1008.3 \(5\)]
)/Contents(Provide exterior egress lighting at all egress exits. Exterior egress fixtures shall be connected to life safety and/or battery-back up. If existing, provide this information on the plans. [VCC 1008.3 \(5\)])/M(D:20190814130816-04'00')/AP<>/NM(XPOASQSFLOGYCDWD)>> endobj 5616 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Show circuit connections for exit and egress lighting on the plans. See Annex B-E2. [NEC 700.12\(F\)]
)/Contents(Show circuit connections for exit and egress lighting on the plans. See Annex B-E2. [NEC 700.12\(F\)])/M(D:20190814130816-04'00')/AP<>/NM(VAWORKQVHGGUCYIT)>> endobj 5621 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Show input watts for all fixture types in the lighting fixture schedule. [VECC C405.4.1, C405.5.1]
)/Contents(Show input watts for all fixture types in the lighting fixture schedule. [VECC C405.4.1, C405.5.1])/M(D:20190814130816-04'00')/AP<>/NM(DGPSNWVVQQKWHLAS)>> endobj 5626 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Show all lighting fixture types in lighting fixture schedule. [VECC C405.4.1, C405.5.1]
)/Contents(Show all lighting fixture types in lighting fixture schedule. [VECC C405.4.1, C405.5.1])/M(D:20190814130816-04'00')/AP<>/NM(OVWEWHYJJSWVTATH)>> endobj 5631 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Transfer switches shall be permitted to be installed in the normal electrical service room where twice the clearance required by article 110.26\(a\) of NFPA 70 \(NEC\) exists between equipment enclosure [NFPA 110 7.2.3]
)/Contents(Transfer switches shall be permitted to be installed in the normal electrical service room where twice the clearance required by article 110.26\(a\) of NFPA 70 \(NEC\) exists between equipment enclosure [NFPA 110 7.2.3])/M(D:20190814130816-04'00')/AP<>/NM(YOUMZITAWDHMILLF)>> endobj 5636 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Emergency Power Supply System equipment shall not be installed in the same room where the normal electrical service equipment in installed. [NFPA 110 7.2.3]
)/Contents(Emergency Power Supply System equipment shall not be installed in the same room where the normal electrical service equipment in installed. [NFPA 110 7.2.3])/M(D:20190814130816-04'00')/AP<>/NM(JPPHUVGMUQXKRZEI)>> endobj 5641 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4No other equipment, including architectural appurtenances, except those that serve this space, shall be permitted in this room. [NFPA 110 7.2.1.3]
)/Contents(No other equipment, including architectural appurtenances, except those that serve this space, shall be permitted in this room. [NFPA 110 7.2.1.3])/M(D:20190814130816-04'00')/AP<>/NM(CFORQCVGYYSBEBSZ)>> endobj 5646 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4The generator room shall have a minimum 2-hour fire rating or be located in an adequate enclosure located outside the building capable or resisting the entrance of snow or rain at a maximum wind velocity required by local building codes. [NFPA 110 7.2.1.1]
)/Contents(The generator room shall have a minimum 2-hour fire rating or be located in an adequate enclosure located outside the building capable or resisting the entrance of snow or rain at a maximum wind velocity required by local building codes. [NFPA 110 7.2.1.1])/M(D:20190814130816-04'00')/AP<>/NM(NFDLGNBTSYUPKIKK)>> endobj 5651 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For Emergency \(NEC Article 700\) and Legally Required \(NEC 701\) Loads, where an outdoor housed generator set is equipped with a readily accessible disconnecting means located within sight of the building or structure supplied, an additional disconnecting means shall not be required where ungrounded conductors serve or pass through the building or structure. The disconnecting means shall meet the requirements of 225.36. Specify the NEC Article \(700, 701, 702, etc.\), to specify the use of the generator, on the plan\(s\). [NEC 700.12 \(B\)\(5\), NEC 701.12 \(B\)\(6\)]
)/Contents(For Emergency \(NEC Article 700\) and Legally Required \(NEC 701\) Loads, where an outdoor housed generator set is equipped with a readily accessible disconnecting means located within sight of the building or structure supplied, an additional disconnecting means shall not be required where ungrounded conductors serve or pass through the building or structure. The disconnecting means shall meet the requirements of 225.36. Specify the NEC Article \(700, 701, 702, etc.\), to specify the use of the generator, on the plan\(s\). [NEC 700.12 \(B\)\(5\), NEC 701.12 \(B\)\(6\)])/M(D:20190814130816-04'00')/AP<>/NM(RHGOOQAOADSJPDSX)>> endobj 5656 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Rooms containing fire pumps shall be free from storage and penetrations not essential to the operation of the pump and related components. [NFPA 20 4.12.1.1.4]
)/ContentsIndoor fire pumps in non-high-rise buildings shall be physically separated or protected by fire rated construction in accordance with Table 5.12.1.1.2. [NFPA 20 4.12.1.1.2]
)/Contents(Indoor fire pumps in non-high-rise buildings shall be physically separated or protected by fire rated construction in accordance with Table 5.12.1.1.2. [NFPA 20 4.12.1.1.2])/M(D:20190814130816-04'00')/AP<>/NM(CBIJKYBJWMNAMDGV)>> endobj 5666 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Comply with NEC 695.6 \(A\) and \(B\). [NEC 695.6 \(A\), \(B\)]
)/Contents(Comply with NEC 695.6 \(A\) and \(B\). [NEC 695.6 \(A\), \(B\)])/M(D:20190814130816-04'00')/AP<>/NM(YJOMVSRAHEUWEOVC)>> endobj 5671 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Transformer size in accordance with NEC Article 450.3, feeder size in accordance with NEC Article 215.3, overcurrent protection device shall be selected or set to carry indefinitely the sum of the
locked-rotor current of the fire pump motor\(s\), the full-load current of the associated fire pump accessory equipment, and 100 percent of the remaining loads supplied by the transformer. [NEC 695.5 \(C\)\(2\)]
)/ContentsProvide sufficient detail on the plan\(s\) to show how the fire pump will be protected from interruption. [NEC 695.3]
)/Contents(Provide sufficient detail on the plan\(s\) to show how the fire pump will be protected from interruption. [NEC 695.3])/M(D:20190814130816-04'00')/AP<>/NM(LFPLKXWTJGHCBZRQ)>> endobj 5681 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Transformers larger than 112.5KVA shall be located in a fire rated room. See exceptions for transform- ers with insulation class of 155 or greater. Provide proper documentation, on the plan\(s\) on how the transformer meets any exceptions. [NEC 450.21\(B\)]
)/M(D:20190814130816-04'00')/AP<>/NM(IXTSPIBMZMHLMUTZ)>> endobj 5686 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For equipment located in either a damp or wet location, provide proper protection for that equipment based on the requirements in Chapter 4 of the National Electrical Code. [NEC Chapter 4]
)/Contents(For equipment located in either a damp or wet location, provide proper protection for that equipment based on the requirements in Chapter 4 of the National Electrical Code. [NEC Chapter 4])/M(D:20190814130816-04'00')/AP<>/NM(YCXCKGDSKCAFIJCX)>> endobj 5691 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide, on the plan\(s\), the wiring methods, including raceway, conductors, and conductor insulation type, unless provided in specifications. [NEC Chapter 3]
)/Contents(Provide, on the plan\(s\), the wiring methods, including raceway, conductors, and conductor insulation type, unless provided in specifications. [NEC Chapter 3])/M(D:20190814130816-04'00')/AP<>/NM(AZNLDEHFXWBGALDA)>> endobj 5696 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For all dwelling units, provide proper receptacle spacing and required receptacle locations. [NEC 210.52]
)/Contents(For all dwelling units, provide proper receptacle spacing and required receptacle locations. [NEC 210.52])/M(D:20190814130816-04'00')/AP<>/NM(OIIBGMDRPHMYHKEJ)>> endobj 5701 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide proper GFCI and AFCI Protection. [NEC 210.08, 210.12]
)/Contents(Provide proper GFCI and AFCI Protection. [NEC 210.08, 210.12])/M(D:20190814130816-04'00')/AP<>/NM(KQSNNKSUAHVMGIDX)>> endobj 5706 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide size of conductors/raceway for branch circuits that are not shown in the panel schedule. [VUSBC 109.3]
)/Contents(Provide size of conductors/raceway for branch circuits that are not shown in the panel schedule. [VUSBC 109.3])/M(D:20190814130816-04'00')/AP<>/NM(UACLRRJVCAARFFQE)>> endobj 5711 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Check for too many fixtures and receptacles on a circuit. [NEC 210.20, 220.14 \(I\)]
)/Contents(Check for too many fixtures and receptacles on a circuit. [NEC 210.20, 220.14 \(I\)])/M(D:20190814130816-04'00')/AP<>/NM(NMYFSYZGDVALPCKD)>> endobj 5716 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Show circuit number at each branch device, if not clear by the homerun. See Annex B-E2, E3.
)/Contents(Show circuit number at each branch device, if not clear by the homerun. See Annex B-E2, E3.)/M(D:20190814130816-04'00')/AP<>/NM(VQWOHTFSKDMYIXSU)>> endobj 5721 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Show all homeruns, listing the circuit numbers and panel they are associated with. See Annex B-E2, E3. [NEC 310.15\(B\)\(3\) \(a\), \(B\)\(3\)\(b\)]
)/Contents(Show all homeruns, listing the circuit numbers and panel they are associated with. See Annex B-E2, E3. [NEC 310.15\(B\)\(3\) \(a\), \(B\)\(3\)\(b\)])/M(D:20190814130816-04'00')/AP<>/NM(EBVJTFGIZBSRVQVV)>> endobj 5726 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For all new panels, indicate voltage, phase, size in amps and AIC rating in the panelboard schedule. For MLO panels, provide withstand current rating. [NEC 110.3]
)/Contents(For all new panels, indicate voltage, phase, size in amps and AIC rating in the panelboard schedule. For MLO panels, provide withstand current rating. [NEC 110.3])/M(D:20190814130816-04'00')/AP<>/NM(ERZBJPCWVUDFXZJT)>> endobj 5731 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Indicate main lugs only \(MLO\), main fuse, or main circuit breaker \(MCB\) size in the panelboard schedule. [NEC 110.3]
)/Contents(Indicate main lugs only \(MLO\), main fuse, or main circuit breaker \(MCB\) size in the panelboard schedule. [NEC 110.3])/M(D:20190814130816-04'00')/AP<>/NM(FAYXHBCZXGYYBQQV)>> endobj 5736 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Show panelboard location\(s\) on floor plan\(s\). [NEC 110.26]
)/Contents(Show panelboard location\(s\) on floor plan\(s\). [NEC 110.26])/M(D:20190814130816-04'00')/AP<>/NM(AHFHGYHWHAKIAHZC)>> endobj 5741 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide, on the plan\(s\), panelboard schedule with loads in amps or KVA \(indicate which\) fuse or circuit breaker sizes and wire sizes - See Annex B-E5. Panelboard schedules are required for all new projects and for renovations projects that will be modifying circuit numbers and circuit locations. [NEC 220]
)/Contents(Provide, on the plan\(s\), panelboard schedule with loads in amps or KVA \(indicate which\) fuse or circuit breaker sizes and wire sizes - See Annex B-E5. Panelboard schedules are required for all new projects and for renovations projects that will be modifying circuit numbers and circuit locations. [NEC 220])/M(D:20190814130816-04'00')/AP<>/NM(KONSGRRNRBGKHQSD)>> endobj 5746 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4"Series ratings shall not be used where:
1\) Motors are connected on the load side of the higher-rated overcurrent device and on the line side of the lower-rated overcurrent device, and
2\) The sum of the motor full-load currents exceeds 1 percent of the interrupting rating of the lower-rated circuit breaker. [NEC 240.86 \(C\)]
)/ContentsFor calculated applications, the professional engineer shall provide these calculations with the documentation on how devices meet the series rating. [NEC 240.86 \(A\)]
)/Contents(For calculated applications, the professional engineer shall provide these calculations with the documentation on how devices meet the series rating. [NEC 240.86 \(A\)])/M(D:20190814130816-04'00')/AP<>/NM(MLLQTKVURFTKKQUT)>> endobj 5756 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Professional Engineer shall provide documentation on how devices meet the series rating. [NEC 240.86\(A\)]
)/Contents(Professional Engineer shall provide documentation on how devices meet the series rating. [NEC 240.86\(A\)])/M(D:20190814130816-04'00')/AP<>/NM(WYJOEJFFMANMNBOK)>> endobj 5761 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Series rated combination devices shall be selected by a professional engineer. [NEC 240.86\(A\)]
)/Contents(Series rated combination devices shall be selected by a professional engineer. [NEC 240.86\(A\)])/M(D:20190814130816-04'00')/AP<>/NM(HNIDHJDEOJDQPOFZ)>> endobj 5766 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide proper overcurrent protection for taps supplying a transformer. [NEC 240.21\(B\)\(3\), 240.21\(C\)\(5\)]
)/Contents(Provide proper overcurrent protection for taps supplying a transformer. [NEC 240.21\(B\)\(3\), 240.21\(C\)\(5\)])/M(D:20190814130816-04'00')/AP<>/NM(CYQNWGWXRSHWYMAJ)>> endobj 5771 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4A set of conductors feeding a single load, or each set of conductors feeding separate loads, shall be permitted to be connected to a transformer secondary, without overcurrent protection at the secondary, as specified in NEC 240.21\(C\)\(1\) through \(C\)\(6\). The provisions of NEC 240.4\(B\) shall not be permitted for transformer secondary conductors. [NEC 240.21\(C\)]
)/Contents(A set of conductors feeding a single load, or each set of conductors feeding separate loads, shall be permitted to be connected to a transformer secondary, without overcurrent protection at the secondary, as specified in NEC 240.21\(C\)\(1\) through \(C\)\(6\). The provisions of NEC 240.4\(B\) shall not be permitted for transformer secondary conductors. [NEC 240.21\(C\)])/M(D:20190814130816-04'00')/AP<>/NM(AYMOARIMNZWSLLFK)>> endobj 5776 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Conductors shall be permitted to be tapped, without overcurrent protection at the tap, to a feeder as specified in NEC 240.21\(B\)\(1\) through \(B\)\(5\). The provisions of NEC 240.4\(B\) shall not be permitted for tap conductors. [NEC 240.21\(B\)]
)/Contents(Conductors shall be permitted to be tapped, without overcurrent protection at the tap, to a feeder as specified in NEC 240.21\(B\)\(1\) through \(B\)\(5\). The provisions of NEC 240.4\(B\) shall not be permitted for tap conductors. [NEC 240.21\(B\)])/M(D:20190814130816-04'00')/AP<>/NM(IFLAMVRQGTVGHDOX)>> endobj 5781 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Ground fault protection of equipment shall be provided in accordance with the provisions of NEC 230.95 for solidly grounded wye electrical systems of more than 150 volts to ground but not exceeding 600 volts phase-to-phase for each individual device used as a building or structure main disconnecting means rated 1000 amperes or more. [NEC 240.13]
)/Contents(Ground fault protection of equipment shall be provided in accordance with the provisions of NEC 230.95 for solidly grounded wye electrical systems of more than 150 volts to ground but not exceeding 600 volts phase-to-phase for each individual device used as a building or structure main disconnecting means rated 1000 amperes or more. [NEC 240.13])/M(D:20190814130816-04'00')/AP<>/NM(VKZKCOUHNXDXPNGK)>> endobj 5786 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Single-phase \(other than 2-wire\) and multiphase \(other than delta-delta, 3-wire\) transformer secondary conductors shall not be considered to be protected by the primary overcurrent protective device. [NEC 240.4\(F\)]
)/ContentsWhere the overcurrent device is rated over 800 amperes, the ampacity of the conductors it protects shall be equal to or greater than the rating of the overcurrent device defined in NEC 240.6. [NEC 240.4\(C\)]
)/Contents(Where the overcurrent device is rated over 800 amperes, the ampacity of the conductors it protects shall be equal to or greater than the rating of the overcurrent device defined in NEC 240.6. [NEC 240.4\(C\)])/M(D:20190814130816-04'00')/AP<>/NM(BYEYHKEUVKHOISIE)>> endobj 5796 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For overcurrent devices rated 800 amperes or less, the next higher standard overcurrent device rating shall be permitted to be used based on all conditions of 240.5\(B\) are met. [NEC 240.4\(B\)]
)/Contents(For overcurrent devices rated 800 amperes or less, the next higher standard overcurrent device rating shall be permitted to be used based on all conditions of 240.5\(B\) are met. [NEC 240.4\(B\)])/M(D:20190814130816-04'00')/AP<>/NM(APHQCUCQWQCOHETP)>> endobj 5801 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For all permanently connected devices greater than 300VA, provide disconnect means within site of the device. [NEC 422.31 \(B\), \(C\)]
)/Contents(For all permanently connected devices greater than 300VA, provide disconnect means within site of the device. [NEC 422.31 \(B\), \(C\)])/M(D:20190814130816-04'00')/AP<>/NM(GJFHFWHPHCEWZUPG)>> endobj 5806 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For safety/disconnect switches and motor starters provide size, type \(i.e. fused/non-fused\), overcurrent protection device size \(if applicable\), and NEMA rating on the plan\(s\). [NEC 110.3]
)/Contents(For safety/disconnect switches and motor starters provide size, type \(i.e. fused/non-fused\), overcurrent protection device size \(if applicable\), and NEMA rating on the plan\(s\). [NEC 110.3])/M(D:20190814130816-04'00')/AP<>/NM(WBJUXPMBHXJCDVKL)>> endobj 5811 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Show location of all safety/disconnect switches and motor starters on the floor plan\(s\) - in sight of equipment. See Annex B-E3. [NEC 110.26, NEC 240.21]
)/Contents(Show location of all safety/disconnect switches and motor starters on the floor plan\(s\) - in sight of equipment. See Annex B-E3. [NEC 110.26, NEC 240.21])/M(D:20190814130816-04'00')/AP<>/NM(QTWESFVZXHPQPXEZ)>> endobj 5816 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4The service disconnecting means shall be located within the nearest point the conductors enter the building. There shall not be any greater than six feet of unprotected conductors from when the service enters the building to the service disconnecting means. [NEC 230.70\(A\)\(1\)]
)/Contents(The service disconnecting means shall be located within the nearest point the conductors enter the building. There shall not be any greater than six feet of unprotected conductors from when the service enters the building to the service disconnecting means. [NEC 230.70\(A\)\(1\)])/M(D:20190814130816-04'00')/AP<>/NM(FAOBFYNNGAIORGMT)>> endobj 5821 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide grounding/bonding requirements for permanently installed pools, spas, hot tubs, and fountains based on Article 680. [NEC 680]
)/Contents(Provide grounding/bonding requirements for permanently installed pools, spas, hot tubs, and fountains based on Article 680. [NEC 680])/M(D:20190814130816-04'00')/AP<>/NM(HBRUXNXEZRIESVSK)>> endobj 5826 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Equipment grounding conductors shall not be smaller than shown in Table 250.122, but in no case shall they be required to be larger than the circuit conductors supplying the equipment. [NEC 250.122]
)/Contents(Equipment grounding conductors shall not be smaller than shown in Table 250.122, but in no case shall they be required to be larger than the circuit conductors supplying the equipment. [NEC 250.122])/M(D:20190814130816-04'00')/AP<>/NM(THSDNGWYHIHKNSVR)>> endobj 5831 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4The size of the grounding electrode conductor at the service, at each building or structure where supplied by a feeder\(s\) or branch circuit\(s\), or at a separately derived system of a grounded or ungrounded ac system shall not be less than given in Table 250.66, except as permitted in 250.66\(A\) through \(C\). [NEC 250.66]
)/Contents(The size of the grounding electrode conductor at the service, at each building or structure where supplied by a feeder\(s\) or branch circuit\(s\), or at a separately derived system of a grounded or ungrounded ac system shall not be less than given in Table 250.66, except as permitted in 250.66\(A\) through \(C\). [NEC 250.66])/M(D:20190814130816-04'00')/AP<>/NM(KLBAXIBZJUKNFFJM)>> endobj 5836 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Where an ac system is connected to a grounding electrode in or at a building or structure, the same electrode shall be used to ground conductor enclosures and equipment in or on that building or structure. Where separate services, feeders, or branch circuits supply a building and are required to be connected to a grounding electrode\(s\), the same grounding electrode\(s\) shall be used. [NEC 250.58]
)/Contents(Where an ac system is connected to a grounding electrode in or at a building or structure, the same electrode shall be used to ground conductor enclosures and equipment in or on that building or structure. Where separate services, feeders, or branch circuits supply a building and are required to be connected to a grounding electrode\(s\), the same grounding electrode\(s\) shall be used. [NEC 250.58])/M(D:20190814130816-04'00')/AP<>/NM(TISZQVBGEGZARJRM)>> endobj 5841 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4"All grounding electrodes as described in 250.52\(A\)\(1\) through \(A\)\(7\) that are present at each building or structure shall be bonded together to form the grounding electrode system. Where none of these grounding electrodes exist, one or more of the grounding electrodes specified in 250.52\(A\)\(4\)through \(A\)\(8\) shall be installed and used. [NEC 250.50]
)/Contents("All grounding electrodes as described in 250.52\(A\)\(1\) through \(A\)\(7\) that are present at each building or structure shall be bonded together to form the grounding electrode system. Where none of these grounding electrodes exist, one or more of the grounding electrodes specified in 250.52\(A\)\(4\)through \(A\)\(8\) shall be installed and used. [NEC 250.50])/M(D:20190814130816-04'00')/AP<>/NM(ASZOVLGDCPEXYLAW)>> endobj 5846 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Building\(s\) or structure\(s\) supplied by feeder\(s\) or branch circuit\(s\) shall have a grounding electrode or grounding electrode system. The grounding electrode conductor\(s\) shall be connected in accordance with NEC 250.32\(B\) or \(C\). [NEC 250.32]
)/Contents(Building\(s\) or structure\(s\) supplied by feeder\(s\) or branch circuit\(s\) shall have a grounding electrode or grounding electrode system. The grounding electrode conductor\(s\) shall be connected in accordance with NEC 250.32\(B\) or \(C\). [NEC 250.32])/M(D:20190814130816-04'00')/AP<>/NM(GYFWXCWBSVPOKHYJ)>> endobj 5851 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Structural steel and metal piping shall be connected to the grounded conductor of a separately derived system in accordance with 250.104\(D\). [NEC 250.30 \(A\)\(8\)]
)/Contents(Structural steel and metal piping shall be connected to the grounded conductor of a separately derived system in accordance with 250.104\(D\). [NEC 250.30 \(A\)\(8\)])/M(D:20190814130816-04'00')/AP<>/NM(SIVFUGUIPBKNAECB)>> endobj 5856 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For parallel conductors, the size of the grounded conductor in each raceway shall be based on the total circular mil area of the parallel ungrounded conductors in the raceway, as indicated in 250.24 \(C\)\(1\), but not smaller than 1/0 AWG. [NEC 250.24 \(C\)\(2\)]
)/Contents(For parallel conductors, the size of the grounded conductor in each raceway shall be based on the total circular mil area of the parallel ungrounded conductors in the raceway, as indicated in 250.24 \(C\)\(1\), but not smaller than 1/0 AWG. [NEC 250.24 \(C\)\(2\)])/M(D:20190814130816-04'00')/AP<>/NM(SIJFFMQNZVFOCTSO)>> endobj 5861 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Size of service grounding electrode conductor shall be based on Table 250.102\(C\)\(1\), but shall not be required to be larger than the largest ungrounded service-entrance conductor. [NEC 250.24 \(C\)\(1\)]
)/ContentsFor generators and transfer switch\(es\), specify the NEC Article \(700, 701, 702, etc.\) next to the generator and/or transfer switch\(es\), to specify the use of the generator/transfer switch\(es\), in the one-line diagram. [NEC 240.12, 240.100, 517.17, 517.30 \(G\), 620.62, 645.27, 700.27/700.28, 701.27, 702, 708.54]
)/ContentsSize the grounding electrode conductors for both services and separately derived systems on the one-line/riser diagram. Do not say \215size per NEC\216. [NEC 250.66, 250.122]
)/Contents(Size the grounding electrode conductors for both services and separately derived systems on the one-line/riser diagram. Do not say \215size per NEC\216. [NEC 250.66, 250.122])/M(D:20190814130816-04'00')/AP<>/NM(DJFZJWTFRSIFJKFC)>> endobj 5876 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Show fault current at all new equipment and devices \(for a service change, then show the AIC rating for all equipment and devices\) in the one-line/riser diagram. For equipment downstream of the service or new equipment and devices, show fault currents down to less than 10KAIC. You are not required to show the fault current for any equipment that is on the load side of the equipment/device that is below 10KAIC. Provide a PDF of Dominion Virginia Power\220s Fault Current Letter so that we may verify your fault current on the plans.
[NEC 110.9]
)/ContentsShow all utilized grounding electrodes and their types in the one-line/riser diagram. For building steel, make sure the plan specifies the method used for considering the building steel as a grounding electrode [i.e. either NEC 250.52 \(A\)\(2\)\(1\) or 250.52 \(A\)\(2\)\(2\)]. If there is a separate Grounding System Diagram, make sure this is located on the same plan as the one-line/riser diagram. [NEC 250.52, 250.52 \(A\)\(2\)]
)/Contents(Show all utilized grounding electrodes and their types in the one-line/riser diagram. For building steel, make sure the plan specifies the method used for considering the building steel as a grounding electrode [i.e. either NEC 250.52 \(A\)\(2\)\(1\) or 250.52 \(A\)\(2\)\(2\)]. If there is a separate Grounding System Diagram, make sure this is located on the same plan as the one-line/riser diagram. [NEC 250.52, 250.52 \(A\)\(2\)])/M(D:20190814130816-04'00')/AP<>/NM(KCBIZJGXYPINNXMK)>> endobj 5886 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Show AIC rating of all new equipment and devices \(for a service change, then show the AIC rating for all equipment and devices\) in the one-line/riser diagram. For equipment with no overcurrent protection, provide equipment withstand current rating on the one-line diagram. [NEC 110.9]
)/Contents(Show AIC rating of all new equipment and devices \(for a service change, then show the AIC rating for all equipment and devices\) in the one-line/riser diagram. For equipment with no overcurrent protection, provide equipment withstand current rating on the one-line diagram. [NEC 110.9])/M(D:20190814130816-04'00')/AP<>/NM(AFMELZBCUAZOHMUA)>> endobj 5891 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Specify either Main Lug Only \(MLO\) or Main Circuit Breaker \(MCB\) and panel amperage for all new
and revised panels in the one-line/riser diagram. [VUSBC 109.3]
)/ContentsFor Transformers, indicate size in KVA, primary and secondary voltages, conductor size \(grounding electrode conductor as well\) , raceway size, and provide grounding electrode that the transformer will be bonded to in the one-line/riser diagram. If there is a separate Transformer Schedule, make sure this is located on the same plan as the one-line/riser diagram. [NEC 110.3, 250.52]
)/Contents(For Transformers, indicate size in KVA, primary and secondary voltages, conductor size \(grounding electrode conductor as well\) , raceway size, and provide grounding electrode that the transformer will be bonded to in the one-line/riser diagram. If there is a separate Transformer Schedule, make sure this is located on the same plan as the one-line/riser diagram. [NEC 110.3, 250.52])/M(D:20190814130816-04'00')/AP<>/NM(ZHWEUSMOFMNPUJGD)>> endobj 5901 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4When Aluminum is allowed in lieu of Copper for service and feeder conductors, specify both the Copper and the Aluminum conductor/raceway size\(s\) on the one-line diagram. A table of the conductor/raceway size\(s\) is acceptable as well, as long as it is located on the same plan as the one-line diagram. [NEC 310.15]
)/Contents(When Aluminum is allowed in lieu of Copper for service and feeder conductors, specify both the Copper and the Aluminum conductor/raceway size\(s\) on the one-line diagram. A table of the conductor/raceway size\(s\) is acceptable as well, as long as it is located on the same plan as the one-line diagram. [NEC 310.15])/M(D:20190814130816-04'00')/AP<>/NM(HZQYBAIYLRLLQINB)>> endobj 5906 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4All Feeders shall be shown on the one-line/riser diagram, with size/type conductors \(including insulation type\) and raceways. If there is a separate Feeder Schedule, make sure this is located on the same plan as the one-line/riser diagram. [NEC 310.15, 250.122]
)/Contents(All Feeders shall be shown on the one-line/riser diagram, with size/type conductors \(including insulation type\) and raceways. If there is a separate Feeder Schedule, make sure this is located on the same plan as the one-line/riser diagram. [NEC 310.15, 250.122])/M(D:20190814130816-04'00')/AP<>/NM(ZOWICJPSPTRUCLAE)>> endobj 5911 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Show all overcurrent protection device sizes \(branch circuit overcurrent protection devices are not required in the one-line/riser diagram\), safety/disconnect switch sizes, raceway and conductor sizes, wireway and trough sizes in the one-line/riser diagram. All overcurrent protection devices protecting feeders shall be shown on the one-line/riser diagram. [NEC 240, NEC Chapter 3]
)/ContentsProvide one-line/riser diagram for any new or revised service\(s\) on the plan\(s\). [VUSBC 109.3]
)/Contents(Provide one-line/riser diagram for any new or revised service\(s\) on the plan\(s\). [VUSBC 109.3])/M(D:20190814130816-04'00')/AP<>/NM(KAGTPJHFKUNHFIVA)>> endobj 5921 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide all new equipment/devices between service and feeder conductors and existing equipment that are on the load and supply side of the new equipment, on the on one-line/riser diagram. [VUSBC 109.3, NEC 110.3, 110.9]
)/Contents(Provide all new equipment/devices between service and feeder conductors and existing equipment that are on the load and supply side of the new equipment, on the on one-line/riser diagram. [VUSBC 109.3, NEC 110.3, 110.9])/M(D:20190814130816-04'00')/AP<>/NM(XKXGFTTCNQNHCNGF)>> endobj 5926 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For project with pole mounted lighting fixtures, provide detail showing pole mount. State depth of conductors/raceway in the detail. [VUSBC 109.3, NEC 300.50]
)/Contents(For project with pole mounted lighting fixtures, provide detail showing pole mount. State depth of conductors/raceway in the detail. [VUSBC 109.3, NEC 300.50])/M(D:20190814130816-04'00')/AP<>/NM(IYKEEGFCTGHLUNSF)>> endobj 5931 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4All underground duct banks shall be shown on the plan. Provide detail for the duct bank on the plan. [VUSBC 109.3]
)/Contents(All underground duct banks shall be shown on the plan. Provide detail for the duct bank on the plan. [VUSBC 109.3])/M(D:20190814130816-04'00')/AP<>/NM(CLKYRYNPAJOUMHFP)>> endobj 5936 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Any site electrical work that encroaches on public land, shall apply for an encroachment through the Department of Public Works.
)/Contents(Any site electrical work that encroaches on public land, shall apply for an encroachment through the Department of Public Works.)/M(D:20190814130816-04'00')/AP<>/NM(HJVJLJZKWIZVWNED)>> endobj 5941 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Show all wiring/raceway sizes, along with burial depths, if installed underground. [NEC 300.5]
)/Contents(Show all wiring/raceway sizes, along with burial depths, if installed underground. [NEC 300.5])/M(D:20190814130816-04'00')/AP<>/NM(UVBEKAODSUCGXJBC)>> endobj 5946 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Show any parking lot lighting, site lighting, and signage. [VUSBC 109.3]
)/Contents(Show any parking lot lighting, site lighting, and signage. [VUSBC 109.3])/M(D:20190814130816-04'00')/AP<>/NM(ZOGGXFLBDYYDFOBF)>> endobj 5951 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Show outline of building, along with any streets, alleys, and property lines. [VUSBC 109.3]
)/Contents(Show outline of building, along with any streets, alleys, and property lines. [VUSBC 109.3])/M(D:20190814130816-04'00')/AP<>/NM(XJEYBFORJGQOFRVO)>> endobj 5956 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For all circuits, switches, receptacles, fixtures, and other electrical components and equipment installed below the design flood elevation shall be energized from a common distribution panel located above and accessible from above the design flood elevation. Provide the location of the common distribution panel along with the Base Flood Elevation \(BFE\) and Design Flood Elevation \(DFE\) on the plan\(s\). [ASCE 24-14 7.2.5]
)/Contents(For all circuits, switches, receptacles, fixtures, and other electrical components and equipment installed below the design flood elevation shall be energized from a common distribution panel located above and accessible from above the design flood elevation. Provide the location of the common distribution panel along with the Base Flood Elevation \(BFE\) and Design Flood Elevation \(DFE\) on the plan\(s\). [ASCE 24-14 7.2.5])/M(D:20190814130816-04'00')/AP<>/NM(OLBQXIDNURTKIZMG)>> endobj 5961 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Show floor/level elevations and flood elevations on each plan, or provide elevation detail showing this information. [VUSBC 109.3, ASCE 24-14]
)/ContentsShow Design Flood Elevation \(DFE\) with the required project information \(see Section A-1\) OR state \215Not in flood plain\216 on plans. DFE shall be based on ASCE 24-14 Table 1-1 and ASCE 24-14 Table 7-1. [VCC 1612, NEC 110.28, ASCE 24-14]
)/Contents(Show Design Flood Elevation \(DFE\) with the required project information \(see Section A-1\) OR state \215Not in flood plain\216 on plans. DFE shall be based on ASCE 24-14 Table 1-1 and ASCE 24-14 Table 7-1. [VCC 1612, NEC 110.28, ASCE 24-14])/M(D:20190814130816-04'00')/AP<>/NM(VKPKXYXDJQJGRRDJ)>> endobj 5971 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For projects required to have a path of egress, provide a continuous and unobstructed way of egress travel from any accessible point in the building to a public way. This will be the Accessible Means of Egress. This should be located on the lighting plan. See Annex B-E2. [VCC 202, 1008]
)/Contents(For projects required to have a path of egress, provide a continuous and unobstructed way of egress travel from any accessible point in the building to a public way. This will be the Accessible Means of Egress. This should be located on the lighting plan. See Annex B-E2. [VCC 202, 1008])/M(D:20190814130816-04'00')/AP<>/NM(GXYGFVDPTICOPVUF)>> endobj 5976 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4In Group R-2 occupancies required by Section 907 to have a smoke alarm system, all dwelling units, and sleeping units shall be provided with the capability to support visible alarm notification appliances in accordance with Chapter 10 of ICC A117.1. Such capability shall be permitted to include the potential for future interconnection of the building fire alarm system with the unit smoke alarms, replacement of audible appliances with combination audible/visible appliances, or future extension of the existing wiring form the unit smoke alarm locations to required locations for visible appliances. [VCC 907.5.2.3.3]
)/Contents(In Group R-2 occupancies required by Section 907 to have a smoke alarm system, all dwelling units, and sleeping units shall be provided with the capability to support visible alarm notification appliances in accordance with Chapter 10 of ICC A117.1. Such capability shall be permitted to include the potential for future interconnection of the building fire alarm system with the unit smoke alarms, replacement of audible appliances with combination audible/visible appliances, or future extension of the existing wiring form the unit smoke alarm locations to required locations for visible appliances. [VCC 907.5.2.3.3])/M(D:20190814130816-04'00')/AP<>/NM(VFETEBYGOTTLGFSE)>> endobj 5981 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Smoke Alarm devices in each unit need to be interconnected. Provide note on the plan\(s\) stating this. [VCC 907.2.11.2.3]
)/Contents(Smoke Alarm devices in each unit need to be interconnected. Provide note on the plan\(s\) stating this. [VCC 907.2.11.2.3])/M(D:20190814130816-04'00')/AP<>/NM(RZIKNEVDJJMWTEJR)>> endobj 5986 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Smoke Alarm devices shall be located in each story within a dwelling unit, including basements, but not including crawl spaces and uninhabitable attics. [VCC 7.2.11.2.3]
)/Contents(Smoke Alarm devices shall be located in each story within a dwelling unit, including basements, but not including crawl spaces and uninhabitable attics. [VCC 7.2.11.2.3])/M(D:20190814130816-04'00')/AP<>/NM(NDQMUJEOPTAQRQDK)>> endobj 5991 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Smoke Alarms shall be installed in each room used for sleeping purposes. [VCC 907.2.11.1.2.2]
)/Contents(Smoke Alarms shall be installed in each room used for sleeping purposes. [VCC 907.2.11.1.2.2])/M(D:20190814130816-04'00')/AP<>/NM(REYUPMQOVRWVNHVP)>> endobj 5996 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Smoke Alarms shall be installed on the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms. [VCC 907.2.11.1.2.1]
)/Contents(Smoke Alarms shall be installed on the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms. [VCC 907.2.11.1.2.1])/M(D:20190814130816-04'00')/AP<>/NM(LHRXIIZZHJBKVBJY)>> endobj 6001 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Where walls or partitions are required to have a fire resistance rating, recessed fixtures shall be installed such that the required fire resistance will not be reduced. [VCC 714.3.2]
)/Contents(Where walls or partitions are required to have a fire resistance rating, recessed fixtures shall be installed such that the required fire resistance will not be reduced. [VCC 714.3.2])/M(D:20190814130816-04'00')/AP<>/NM(DZDPRAPRVJWFCALL)>> endobj 6006 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide, on the plan\(s\), UL listed fire stopping detail as found in the latest edition of the UL Fire
Resistance Directory for the type of through penetration used \(see Annex B-E6, Annex C\). See link
below if help is needed: http://productspec.ul.com/index.php?type=firestop [VCC 714.3.2]
)/ContentsIf there are no rated assemblies or no rated assemblies being penetrated, state this on the first
electrical plan. Clearly label all fire rated assemblies, firewalls, fire separation walls as to their rating in hours on all electrical plans. See Annex B-E2, E3. [VCC 714.3.2]
)/ContentsThere is a fee for revisions after the permit has been issued. For projects that are greater than $500.000, there will be a one time fee at the first revision. No other fees will be required for other revisions. For projects under $500,000, a revision fee of 10% of the original permit application fee will be charged for all revisions after permit has been approved.
)/Contents(There is a fee for revisions after the permit has been issued. For projects that are greater than $500.000, there will be a one time fee at the first revision. No other fees will be required for other revisions. For projects under $500,000, a revision fee of 10% of the original permit application fee will be charged for all revisions after permit has been approved.)/M(D:20190814130816-04'00')/AP<>/NM(QXHVPDXFTCSKVKED)>> endobj 6021 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Do not skip revisions, submit all revisions for review that affect the permit when they are issued; do not wait until 2 or 3 revisions have been made to submit for review.
)/Contents(Do not skip revisions, submit all revisions for review that affect the permit when they are issued; do not wait until 2 or 3 revisions have been made to submit for review.)/M(D:20190814130816-04'00')/AP<>/NM(ISBBGMKEHWAJNHLG)>> endobj 6026 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4When a plan reviewer submits comments based on the post-permit plans, make sure NOT to add a new revision number and date. Keep all clouds and triangles based on the original post-permit number and date. If required to add a new revision number, KEEP the same date of the original post-permit submission.
)/Contents(When a plan reviewer submits comments based on the post-permit plans, make sure NOT to add a new revision number and date. Keep all clouds and triangles based on the original post-permit number and date. If required to add a new revision number, KEEP the same date of the original post-permit submission.)/M(D:20190814130816-04'00')/AP<>/NM(QVJWPHRZRDAMSCIJ)>> endobj 6031 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide a complete set of electronic \(PDF\) electrical Construction Documents. Plans shall be in one PDF file and not
have any City stamps from any discipline within the City of Richmond or any other markings that are not original to the
plans. Unless required by the plan reviewer, a checklist is not be required for re-submission. All submitted documents
shall follow the naming convention in Section A-5, page 5. For plans being resubmitted due to comments for a
\215post-permit\216 revision, provide all plans that were submitted for that post-permit revision \(for example if only three
plans were submitted in the post-permit revision, then resubmit those three plans\). All documents being resubmitted
shall be brought into Room 110 at City Hall for processing.
)/ContentsProvide clouds around modifications only \(do not cloud an entire area, since the modification might not affect that entire area, unless it\220s a new plan, in that case cloud the plan number\) with numbered revision triangles and remove clouds from previously approved revision\(s\). See Annex B-E1 for an example.
)/Contents(Provide clouds around modifications only \(do not cloud an entire area, since the modification might not affect that entire area, unless it\220s a new plan, in that case cloud the plan number\) with numbered revision triangles and remove clouds from previously approved revision\(s\). See Annex B-E1 for an example.)/M(D:20190814130816-04'00')/AP<>/NM(NCSKDLSITHMYLOXM)>> endobj 6041 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide a clarification letter, in PDF format with a file name based on Section A-5, Page 5, stating all modifications per each
plan. The clarification letter shall include the plan number, date of the modification, and a detailed description of each
modifications. Cloud each modification separately. Failure to provide this information will delay the permit being issued.
)/ContentsRevised plans are required to be the same size as original plans.
)/Contents(Revised plans are required to be the same size as original plans.)/M(D:20190814130816-04'00')/AP<>/NM(DSVCQQLFYHOPDQFA)>> endobj 6051 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide a complete set \(revised plans/documents only\) of electronic \(PDF\) electrical Construction Documents. Plans shall be in one PDF file and not have any City stamps from any discipline within the City of Richmond or any other markings that are not original to the plans. Complete set of the electrical plans is not required for changes after the permit has been issued. You only need to submit the plans that were modified based on the clarification letter. For re-submitting post-permit plans based on plan review comments, see items 02 through 06 above. Unless required by the plan reviewer, a checklist is not be required for resubmission. All submitted documents shall follow the naming convention in Section A-5, page 5. All documents being submitted shall be brought into Room 110 at City Hall for processing.
)/Contents(Provide a complete set \(revised plans/documents only\) of electronic \(PDF\) electrical Construction Documents. Plans shall be in one PDF file and not have any City stamps from any discipline within the City of Richmond or any other markings that are not original to the plans. Complete set of the electrical plans is not required for changes after the permit has been issued. You only need to submit the plans that were modified based on the clarification letter. For re-submitting post-permit plans based on plan review comments, see items 02 through 06 above. Unless required by the plan reviewer, a checklist is not be required for resubmission. All submitted documents shall follow the naming convention in Section A-5, page 5. All documents being submitted shall be brought into Room 110 at City Hall for processing. )/M(D:20190814130816-04'00')/AP<>/NM(QFHVHBGJBOLWTCYA)>> endobj 6056 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide clouds around response letter modifications only \(do not cloud an entire area, since the modification might not affect that entire area, unless it\220s a new plan, in that case cloud the plan number\) with numbered revision triangles and remove clouds from previously issued revision\(s\). See Annex B-E1 for an example.
)/Contents(Provide clouds around response letter modifications only \(do not cloud an entire area, since the modification might not affect that entire area, unless it\220s a new plan, in that case cloud the plan number\) with numbered revision triangles and remove clouds from previously issued revision\(s\). See Annex B-E1 for an example.)/M(D:20190814130816-04'00')/AP<>/NM(GJBEJNKUFMJRUGFE)>> endobj 6061 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide a response letter, in PDF format with a file name based on Section A-5, Page 5, stating the resolution for each comment
item. All comments shall be addressed in the response letter. Failure to provide this information will delay the permit being
issued. Provide a detail response for each comment item. Responses of \215Will Comply\216, \215Okay\216, \215Noted\216, \215Will Verify\216, \215This
has been complied with\216, and other responses that do not provide a detailed response will not be acceptable responses.
Responses such as those noted, will be sent back for proper responses.
)/ContentsRevised plans are required to be the same size as original plans.
)/Contents(Revised plans are required to be the same size as original plans.)/M(D:20190814130816-04'00')/AP<>/NM(COZQVNFLBIJJAUZD)>> endobj 6071 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide contact information for contractor \(or owner, if owner is applying for the permit\) and engineer \(if applicable\). Required Contact information shall be the following: telephone number, email address, and mailing address. If a business fax number is available, provide this information as well.
)/Contents(Provide contact information for contractor \(or owner, if owner is applying for the permit\) and engineer \(if applicable\). Required Contact information shall be the following: telephone number, email address, and mailing address. If a business fax number is available, provide this information as well.)/M(D:20190814130816-04'00')/AP<>/NM(SCLWODSSVDXVGXYQ)>> endobj 6076 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For all projects listed as class IV in Chapter 16 of the VCC \(Table 1604.5\), provide seismic details for mounting of all emergency equipment and devices. Refer to Section D-3 for Seismic Requirements.
)/Contents(For all projects listed as class IV in Chapter 16 of the VCC \(Table 1604.5\), provide seismic details for mounting of all emergency equipment and devices. Refer to Section D-3 for Seismic Requirements.)/M(D:20190814130816-04'00')/AP<>/NM(AEUXFURBYRFFLRFV)>> endobj 6081 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For projects that require selective coordination, refer to Section D-1 for the City of Richmond\220s requirements for Coordination Studies.
)/Contents(For projects that require selective coordination, refer to Section D-1 for the City of Richmond\220s requirements for Coordination Studies.)/M(D:20190814130816-04'00')/AP<>/NM(SOXIQZAIRDWUQOMJ)>> endobj 6086 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For projects with photovoltaic, see Section D-2 for the City of Richmond\220s plan requirements for photovoltaic projects. Refer to NEC Article 690.
)/Contents(For projects with photovoltaic, see Section D-2 for the City of Richmond\220s plan requirements for photovoltaic projects. Refer to NEC Article 690.)/M(D:20190814130816-04'00')/AP<>/NM(VXLCJNQFYJPMSAIL)>> endobj 6091 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For all patient care projects, provide a list on the plan\(s\) stating which rooms/areas are patient care areas. Provide proper wiring to these locations. Refer to NEC Article 517.
)/Contents(For all patient care projects, provide a list on the plan\(s\) stating which rooms/areas are patient care areas. Provide proper wiring to these locations. Refer to NEC Article 517.)/M(D:20190814130816-04'00')/AP<>/NM(NFHVBJEOVGJSSOMU)>> endobj 6096 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For projects with hazardous areas, show this on the plan\(s\) stating the Class and Division as well. Show an outline of each hazardous area on the plans. Refer to NEC Article 500.
)/Contents(For projects with hazardous areas, show this on the plan\(s\) stating the Class and Division as well. Show an outline of each hazardous area on the plans. Refer to NEC Article 500.)/M(D:20190814130816-04'00')/AP<>/NM(WOUBKIRQYLSBOQEF)>> endobj 6101 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For high-rise buildings, provide all necessary emergency and legally required loads as specified for high-rise buildings on the plan\(s\). Refer to IBC Section 403.
)/Contents(For high-rise buildings, provide all necessary emergency and legally required loads as specified for high-rise buildings on the plan\(s\). Refer to IBC Section 403.)/M(D:20190814130816-04'00')/AP<>/NM(MUVLXLTFIJVIHZTS)>> endobj 6106 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For project with new or revised load\(s\), provide load calculations for entire normal service [provide separate load calculation for new generator\(s\)] on the plan\(s\). For renovation projects, provide existing load based on Article 220.87. Refer to NEC 220, NEC ANNEX D
)/Contents(For project with new or revised load\(s\), provide load calculations for entire normal service [provide separate load calculation for new generator\(s\)] on the plan\(s\). For renovation projects, provide existing load based on Article 220.87. Refer to NEC 220, NEC ANNEX D)/M(D:20190814130816-04'00')/AP<>/NM(QYSQIAWNREBTIXPE)>> endobj 6111 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For dwelling units in multi-use building\(s\) or use groups R2, and R4 with greater than three stories, state on the plan\(s\) how the project is in compliance with IECC C405.1, exception. Provide on the plan\(s\), the percentage of high-efficacy fixtures for each dwelling unit and provide the lumens/watt rating in the fixture schedule.
)/Contents(For dwelling units in multi-use building\(s\) or use groups R2, and R4 with greater than three stories, state on the plan\(s\) how the project is in compliance with IECC C405.1, exception. Provide on the plan\(s\), the percentage of high-efficacy fixtures for each dwelling unit and provide the lumens/watt rating in the fixture schedule.)/M(D:20190814130816-04'00')/AP<>/NM(HDRMSVHUPBJOQUBH)>> endobj 6116 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For all projects \(other than Residential Buildings per VECC\) with any new lighting, provide a COMCheck. Refer to Section E-1 for further description of what is required for energy code compliance.
)/Contents(For all projects \(other than Residential Buildings per VECC\) with any new lighting, provide a COMCheck. Refer to Section E-1 for further description of what is required for energy code compliance.)/M(D:20190814130816-04'00')/AP<>/NM(CRGPPHNVTTVTWOJX)>> endobj 6121 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For multi-level buildings, there shall be a floor plan for each and every level, do not show a \215typical\216 floor plan for multiple levels. The electrical inspector will use this for their inspections.
)/Contents(For multi-level buildings, there shall be a floor plan for each and every level, do not show a \215typical\216 floor plan for multiple levels. The electrical inspector will use this for their inspections.)/M(D:20190814130816-04'00')/AP<>/NM(CORMSJYDAUIQRCJO)>> endobj 6126 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Electrical site work requires plans. All parking lots with lighting \(showing photometrics in parking lot on the plan\(s\)\) shall be routed to Zoning for review. Provide graphical scale on all site plan plans \(see Annex B-E2, E3 for an example\).
)/Contents(Electrical site work requires plans. All parking lots with lighting \(showing photometrics in parking lot on the plan\(s\)\) shall be routed to Zoning for review. Provide graphical scale on all site plan plans \(see Annex B-E2, E3 for an example\).)/M(D:20190814130816-04'00')/AP<>/NM(HINDEOMXLBHQGOUO)>> endobj 6131 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4New work shall be differentiated from that which exists. See Section B-1 for more information. See Annex B-E4, E4A for an example. The plans shall make it clear what is new and what is existing.
)/Contents(New work shall be differentiated from that which exists. See Section B-1 for more information. See Annex B-E4, E4A for an example. The plans shall make it clear what is new and what is existing.)/M(D:20190814130816-04'00')/AP<>/NM(SQBCFCUYIOUDHNCG)>> endobj 6136 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4All Plans shall be signed by the proper individual, and only that individual will sign/seal all plans. See Annex A for a list of all Use Groups and whom can sign these plans. List is based on the Code of Virginia \24754.1-402. Only one signature or signed/seal shall be on each plan.
)/Contents(All Plans shall be signed by the proper individual, and only that individual will sign/seal all plans. See Annex A for a list of all Use Groups and whom can sign these plans. List is based on the Code of Virginia \24754.1-402. Only one signature or signed/seal shall be on each plan.)/M(D:20190814130816-04'00')/AP<>/NM(CJFBNLYKBBAWMDIS)>> endobj 6141 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Within the scope of work, all spaces \(specify dwelling unit numbers\) and rooms shall be labeled, on all the plan\(s\), as to their use. See Annex B-E2, E3 for an example. This includes spaces such as closets, hallways, etc.
)/Contents(Within the scope of work, all spaces \(specify dwelling unit numbers\) and rooms shall be labeled, on all the plan\(s\), as to their use. See Annex B-E2, E3 for an example. This includes spaces such as closets, hallways, etc.)/M(D:20190814130816-04'00')/AP<>/NM(HIZUZJPHXBIHAYPP)>> endobj 6146 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For projects that require specifications, provide only the electrical specifications on the plans. For specifications not on plans, provide an electronic \(PDF\) copy of electrical specifications only. Follow the naming convention in Section A-5, page 5.
)/Contents(For projects that require specifications, provide only the electrical specifications on the plans. For specifications not on plans, provide an electronic \(PDF\) copy of electrical specifications only. Follow the naming convention in Section A-5, page 5.)/M(D:20190814130816-04'00')/AP<>/NM(FSCQMVCXCBQJQNNX)>> endobj 6151 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide a legend for all symbols and abbreviations/acronyms on the plan\(s\). See Annex B-E1 for an example.
)/Contents(Provide a legend for all symbols and abbreviations/acronyms on the plan\(s\). See Annex B-E1 for an example.)/M(D:20190814130816-04'00')/AP<>/NM(SNSYYRVNRFZDJQLV)>> endobj 6156 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide all necessary engineering details on the plan\(s\).
)/Contents(Provide all necessary engineering details on the plan\(s\).)/M(D:20190814130816-04'00')/AP<>/NM(CQTOIETGGDPWOBIO)>> endobj 6161 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4On the first electrical plan, provide all the project information shown in Section A-2. See Annex B-E1 for an example.
)/Contents(On the first electrical plan, provide all the project information shown in Section A-2. See Annex B-E1 for an example.)/M(D:20190814130816-04'00')/AP<>/NM(NMOZHWEFRLCWFAIJ)>> endobj 6166 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4All plans shall have the information shown in the example title block in Section A-1. See Annex B-E1 for an example.
)/Contents(All plans shall have the information shown in the example title block in Section A-1. See Annex B-E1 for an example.)/M(D:20190814130816-04'00')/AP<>/NM(BCQYXFITZBWSFEGH)>> endobj 6171 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4All text on the plans shall be at least 0.125" in height.
Exceptions: Photometrics, superscripts, and subscripts at least 0.1\216 in height.
)/ContentsAll rooms/areas containing new/relocated equipment \(service entrance equipment, electrical panels, transformers, etc.\) are required to show all working clearance space about equipment [NEC 110.26]. See Annex B-E3 for an example. Show all new and existing equipment and any other obstructions \(trees, walls, etc.\) in these rooms/areas. Make sure this is a plan view, not an elevation view \(elevation view is optional unless it is required to show equipment location\(s\)\).
)/Contents(All rooms/areas containing new/relocated equipment \(service entrance equipment, electrical panels, transformers, etc.\) are required to show all working clearance space about equipment [NEC 110.26]. See Annex B-E3 for an example. Show all new and existing equipment and any other obstructions \(trees, walls, etc.\) in these rooms/areas. Make sure this is a plan view, not an elevation view \(elevation view is optional unless it is required to show equipment location\(s\)\).)/M(D:20190814130816-04'00')/AP<>/NM(RTORGQTNOMPRAIZY)>> endobj 6181 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4For project with more than one plan/sheet/plan, provide a list of all plans, on the first electrical plan, stating sheet number and description of the plan. See Annex B-E1 for an example.
)/Contents(For project with more than one plan/sheet/plan, provide a list of all plans, on the first electrical plan, stating sheet number and description of the plan. See Annex B-E1 for an example.)/M(D:20190814130816-04'00')/AP<>/NM(SHHZNBRFKRKHRDMI)>> endobj 6186 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Plans shall be at least 1/8" \(1/8\216 = 1\220-0\216\) scale or larger, other than site plans. Provide a graphical scale\(s\) on all plans that have scaled floorplans. Provide a graphical scale for all different scaled floorplans on each plan \(see Annex B-E2, E3 and E3A for examples\).
)/Contents(Plans shall be at least 1/8" \(1/8\216 = 1\220-0\216\) scale or larger, other than site plans. Provide a graphical scale\(s\) on all plans that have scaled floorplans. Provide a graphical scale for all different scaled floorplans on each plan \(see Annex B-E2, E3 and E3A for examples\).)/M(D:20190814130816-04'00')/AP<>/NM(ITNOXBEBOUMPQLUX)>> endobj 6191 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Plans shall be neat and legible, and shall be all the same size. See Annex B for example plans.
)/Contents(Plans shall be neat and legible, and shall be all the same size. See Annex B for example plans.)/M(D:20190814130816-04'00')/AP<>/NM(UDMHHRQLOWZODQLB)>> endobj 6196 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4Provide a complete set of electronic \(PDF\) electrical Construction Documents on either a thumb drive or CD/DVD. For plans, make sure you have one PDF file of all plans. All plans to be the same size. All submitted documents shall follow the naming convention in Checklist A-5, page 5.
)/Contents(Provide a complete set of electronic \(PDF\) electrical Construction Documents on either a thumb drive or CD/DVD. For plans, make sure you have one PDF file of all plans. All plans to be the same size. All submitted documents shall follow the naming convention in Checklist A-5, page 5.)/M(D:20190820144905-04'00')/AP<>/NM(MQKWAGGEHSASFEFI)>> endobj 6201 0 obj<>>>/Matrix[1 0 0 1 0 0]/Length 344/Filter/FlateDecode>> stream xN0_O`[#b *>SѥSKzs>])pG)|ROí6B CݓЇ.s"\"UΑ>\#Icq,$cLzװXT F Ʃj3R1'KBp-QAާ;g.UluoHm]( bh>vMY1G5 ,q{{+`)s8|ŻU>*w{|4